EGP1,000.00
| Dielectric Test Voltage | 50 / 60 Hz – 1 min 2 kV |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (133 V AC) 20 kA (230 V AC) 10 kA (24 V DC) 20 kA (60 V DC) 10 kA (230 V) 10 kA (400 V) 10 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (133 V AC) 15 kA (230 V AC) 7.5 kA |
| Power Supply Connection | Arbitrary |
| Contact Position Indication | Red ON / Green OFF |
| Energy Limiting Class | 3 |
| Electrical Endurance | 20000 AC cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 1 |
| Number of Poles | 1P |
| Tightening Torque | 2.8 N·m |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Marking | I / O |
| Actuator Material | Insulation Group II, Black, Sealable |
| Recommended Screw Driver | Pozidriv 2 |
| Accessories Available | Yes |
| Connecting Capacity | Busbar 10/10 mm² Flexible with Ferrule 0.75 … 25 mm² Flexible 0.75 … 25 mm² Rigid 0.75 … 35 mm² Rigid 0.75 … 35 mm² Stranded 0.75 … 35 mm² |
| Installation Size | acc. to DIN 43880 1 |
| Wire Stripping Length | 12.5 mm |
| Terminal Type | Screw Terminals |
| Tripping Characteristic | C |
| Rated Operational Voltage | acc. to IEC 60898-1 230 V AC |
| Operational Voltage | Maximum (Incl. Tolerance) 253 V AC Maximum (Incl. Tolerance) 72 V DC Minimum 12 V AC Minimum 12 V DC |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV at 2000 m 5 kV at Sea Level 6.2 kV |
| Input Voltage Type | AC/DC |
| Rated Current (In) | 16 A |
| Rated Short-Circuit Capacity | (AC) 6 kA (DC) 6 kA (230 / 400 V AC) 6 kA |
| Rated Conditional Short-Circuit Current (Inc) | (230 V) 10 kA (400 V) 10 kA |
| Frequency (f) | 50 Hz |
| Rated Frequency (f) | 50 / 60 Hz |
| Power Loss | 2.5 W at Rated Operating Conditions per Pole 2.5 W |
| Overvoltage Category | III |
| I²t Characteristic | S200_S200M_S200P let-through energy B-C |